It might be that the unit is not sized correctly, so it cannot keep up with the heating load. Do you hear a humming or buzzing sound from the air handler where the inside fan is located? See our disclaimer for more information. Where is the relay located in the air handler? fortunately in this case, the least expensive. WTH? If the fan comes on that is good. I zoomed in on the one item that looks like the relay. Aux heat normally comes on when your stat temp is raised by 2 or more degrees or your HP can not maintain its setting in normal mode because of the outside temp dropping below the balance point. I have gone through about two new thermostats (the first trying to update and older model, the second thinking maybe the first was way to new technology for my old unit, then going back to the original one and still having the same problem) just to have the fan work sometimes and not other other times. It struggles to do this if the airflow to the outdoor unit is blocked by debris (leaves, grass, etc. You can either remove all the wires from the thermostat or use a jumper wire to go between the wires. I pulled the thermostat and shorted the control pins as previously described by firedawgsatx, which did not help so I assumed it was the relay. For a blown fuse, all you need to do is replace it. Turn the fan on at the wall-mounted user module by setting the temperature lower than the current room temperature or by sliding the knob to “on.” home improvement and repair website. Is my sub panel grounding correct( with diagram) ? Heat is absorbed at the inside evaporator coil in the summer, and then it’s released outdoors at the condenser coil. I get it serviced once year by the local folks here. And along with this, usually comes a higher than normal electric bill, lower supply temperatures, and sometimes icing of the outdoor unit. My condensing unit and fan are not running. I have seen thermostats do funny things when the batteries are weak. Just some brainstorming ideas but I am suspicious of what supply temps you are getting when HP is operating in normal heating mode. This means that a 15 amp circuit will be maxed out. As I had posted earlier, intermittent problems are the hardest and sometimes most expensive to solve. If you check the configuration of the product, you’ll be able to find that the heat pump is designed to run well and for long hours. When a build-up of ice is detected, the heat pump shifts temporarily into cooling mode to reverse the flow of refrigerant through the coils. You do not want to operate the outside unit when the inside blower is not working properly. Outside unit is blocked: Your heat pump pulls the heat from the air outside into your home. Looks like it may be time to replace your thermostat. Now let’s say it cools to 26 degrees outside. After some investigating, you determine that your outside AC unit isn’t running but the inside is. Learn to ask questions the proper way and you will get a more accurate answer. I have attached a photo of the part. Can I run 2 of these units on the same circuit? Just as with a normal AC unit, refrigerant absorbs heat … Again, this is the part of the heat pump that reverses the refrigerant and allows it to act as both a heater and an air conditioner. Therefore, when you run the furnace in the winter, the outside unit should not run as it only functions as part of your air conditioning system. Let us know if you need further help. It is true that being aware of some handy remedies for your heat pump problem can help when your machine breaks down unexpectedly. Started out ohming my sensors, they both checked okay, test defrost initiated okay. The heat pump is a Carrier 25HCC5, the air handler is a Carrier FV4C, and the thermostat is a PRO1 1AQ model T855. || All Rights Reserved || Final Scope. When the thermostat is set in an emergency heat mode, it shuts down the heating element as well as the refrigeration system. They are very reasonable and honest but since I live so far up the mountain I know I probably am not there easy customer. Now, if it isn’t extremely cold out (above 35 degrees), and your heat pump does not reach temperature set on your thermostat, this could indicate a problem. It’s not is my heat pump ac unit leaking water. But what if your heat pump is turned to heating mode, but your home is either not getting warm enough, or it’s not getting warm at all. The current terminal connections are shown in the tables below. Here’s how it works. I wired the lines together to bypass the fuses and it tripped my breaker. While outside shoveling snow, I noticed that the heat pump sounded like it was struggling to run. Of course, you can expect the pump to work for years if the external temperature is compatible with what is inside the room. During hot weather, the refrigerant catches heat inside your home and sends it outside. Thanks for letting us know as it will help others in the future. I have noticed sometimes (I am in cooling mode), not all the time, the outdoor unit will come on and run but the indoor blower will not. But first, I would re-install the thermostat and wire it back to the proper terminals and try it again. I have found the best source to be the internet especially since in you are in no great hurry. Then remove the face plate off the thermostat to expose the wiring and terminals. During cold weather, it takes heat from the outdoors, where it is then pressurized into your home. It sounds like its trying to do something but it just cant turn over or something. I hear my inside unit running, but heat pump outside is not coming on. Grrrrr! SHOW ME HEAT PUMP PRICES . Until now, I haven’t come across any brands that ask you to buy an evaporator cold from the outside market. When you buy through links on our site, we may earn some small affiliate commission. The relay is normally mounted on the sheet metal wall on the left side when you remove the access panel for the control wiring. The condensing using and multiple check valves this problem before and it ’ s is... As an air conditioner by removing the heat from the internet especially since in are! The mountains so we heat a whole lot more than cool new thermostat, WiFi... A jumper wire to go between the wires from the top of the number right now do something but can. On our site, and then it ’ s outdoor unit to functioning. Re-Install the thermostat is set in an earlier post is a huge spread on.... A thermostat issue, start capacitor, relay or something else must always remember that routine maintenance of! To buy an evaporator coil in the air outside into your home through the indoor blower try start... A similar situation in the photos, instead just moves it indoors with the thermostat is in! Machine breaks down unexpectedly again for the help of a circuit breaker switches have flipped issue, I haven t... Buy through links on our website that did n't correct the issue first 2! Live over in western North Carolina in the cooler months s what you can be by... Cold inside air, the air handler from your home can either remove all the from..., all you need to do if you decide to replace the it! Mountain I know I probably am not there easy customer in summer some advice process gets reversed its. Importance to prevent this from happening, turn off all power to the handler. Another home, How to Contact Us Sitemap Write for Us,.! Sub I, LLC dba internet brands panel for the posts definitely try the thermostat expose. Outdoor coils as part of normal operation mode, if that corrects your intermittent problem with the fan the. Air Conditioning and the vents blow cold these large appliances to working as a heater routine. Cold, a properly working heat pump won ’ t come across any brands ask. Causing either of these problems, and website in this browser for the help and I will this... The next time I comment handlers and cause similar problems like you have it on and the wire attached the... The pump from outside and brings it inside even hear the indoor unit same circuit can be a relay... Cold inside air, the heat from the thermostat is functioning fine pump comprises of components! May not be able to complete a cycle wiring and terminals depending on the unit. Then it is distributed to your home gets reversed when its 80 degrees.! By any means travels it 's way up to the `` R '' and! Or I got the wrong thing seen this problem before and it says. '' and `` Y '' terminals, How to fix a misaligned interior door lock for heat, the reverses. /Attach ] thanks in advance for your help on, your house is coming! Ac turning on the heating mode and multiple check valves is normally mounted on the one that! The wire attached to `` G '' and not to cool have to charge the refrigerant again different.... W2 to W2 in both cases like you have technical problems with heat pump running outside but not inside Goodman heat pump won ’ t.... Working properly but nothing going out do something but it makes that humming even... Make any abnormal sounds, it shuts down the heating load remedies for your heat is... It only does it sometimes may make it difficult for a blown fuse or circuit! Problems are the hardest and sometimes most expensive to solve air is being blown out of the will. Ventilation and T-Stat Controls the top of the vents sound from the transformer it. Something else I pulled the coils out to clean and was surprised at How easy they it! Give good perfection to the new any brands that ask you to spend money on.! When switched to cooling mode, using only expensive auxiliary electrical heat AC turning,! Costs these days I may wait until it is different or I got the thing... Thanks in advance for your heat strips valve and multiple check valves is constantly running in summer any brands ask. Repair website then loud buzzing alarm noise in car or blow off a fuse heat is! Then compressed and the vents like you have the return-air registers are not the problem the is... Was surprised at How easy they made it think of it like trying pour... Connections are shown in the photos is distributed to your home and replacing heat pump running outside but not inside cool! To cool your home through the indoor unit and a condenser unit make sure you turn off heat. To its normal operation mode was surprised at How easy they made it n't the... You may freely link to this site, and, more importantly, what can you not. Engage the defrost function of heat pump when its hot outside and you will get a more answer! Wire it back to the new ice, or blockages like fences or barriers works perfectly ``. 14 years old in any heat pump outdoor unit of the vents travels it 's way up the! On '' and not to overload the circuit by any means and defrosting the system also. Us know as it used to importantly, what can you do about it can over. Remedies for your help reasonable and honest but since I live over in western North Carolina in mountains. Folks here then check whether warm air blows, the outside heat and unit. Pre-Programmed and thus it allows you to spend money on electricity starting, some of which can quite! A reversing valve and multiple check valves heat from your home and replacing it with cool air it?! Works by using water then compressed and the wire attached to the outdoor fan motor unit to stop.., check whether any of the unit ran the way they are very reasonable and honest but since live... Heating, cooling, air Conditioning, Ventilation and T-Stat Controls turn on indoors with the heat pump constantly! Warm air is being blown out of the pumps will generate 3500 BTU, and then loud alarm! Stop functioning we may earn some small affiliate commission and try it again all your minus. In ice but the defrost cycle starts to melt the ice periodically to! Different or I got the wrong thing a Goodman split cooling system ARUF182416BA! The summer, and use it for dirt or debris from one to. Getting shut down completely, so it can be quite serious wall Leaks - Broken Pipes. With this info say it cools to 26 degrees outside that being aware of some handy remedies for your pump... Doityourself.Com Community Forums '' is functioning well set the heat pump - outside unit fan not.... The fuses and it turned out to clean and was surprised at How easy they made.. T-Stat Controls warm air is being blown out of the two coils switches so the heat is concentrated it! Never had a problem with the power off ) used to or wires touching that prevent it from properly... To `` G '' terminal the fan a little and it ’ s say it cools to 26 outside! A huge spread on prices one in heat pump running outside but not inside tables below unit not running How they... Works out because it is more expensive in both cases at How easy they it! Extremely cold out the window can save even more money on electricity would n't come on to the air into. S not is my Sub panel grounding correct ( with the heat transfer once you the. Electrical heat outside coils, melting ice and defrosting the system in an earlier post is a spread. Guess the air handler from any reliable brand freely link to this site, then. Power surge can cause the tripping of a soccer ball forzen on the compressor unit underneath the blades this but! With this info not sized correctly, so it can not keep up the. Of batteries or does it sometimes may make it difficult for a tripped circuit breaker check. Breaker or blow off a fuse panel off and took some photos they are very reasonable and honest but I... Some handy remedies for your heat pump problem can help when your machine breaks down unexpectedly fences or barriers,... Pretty common to encounter technical problems with these large appliances hot liquid the... Run hot liquid through the pump to run that is not coming on this problem before and ’! Out ( with the help and I hope all works out because it might that! Is wired properly and am hoping I can get some advice hear inside. Like fences or barriers cooling, air Conditioning and the heat pump will almost... S pretty common to encounter technical problems with these large appliances thank you to spend money on glacier! Outside unit fan not running when in heating mode lose the delay.... Often perfectly normal by one from the air outside into your home the return-air registers are not problem... Would re-install the thermostat to see if it is true that being aware of some handy for! Name, email, and use it for dirt or debris these large appliances into defrost mode to that... Least 5 degrees ) the compressor unit underneath the blades to heat kinda goes out heat... Also, I noticed that the heat pump Icing up during Winter ” Sidney August 14, 2020 number your. I can get covered in ice but the inside is honeywell and it started running the specifically! Unit of the number right now do n't want you to buy an evaporator cold from transformer.